The short answer
A sauna needs three openings: a supply vent low by the heater, an exhaust vent low on the far wall, and a 4 in drying vent up high that stays shut while you bathe. For the 6 x 7 ft outdoor sauna in the planner that is a 6 in supply and a 12 in exhaust, and the six air changes an hour the heater makers ask for come to about 29 cu ft a minute.
Yes, a sauna needs ventilation, and it is not optional. Heater makers write it into the manual: fresh air in, used air out, and a way to dry the room afterward. This guide gives you the three openings, where each one goes, and how big each one is for the sizes in the planner.
Everything here comes from the heater maker's rules, not from a building code. Your heater's manual wins over this page, and the planner is clear about the one thing it does not do: it does not calculate natural draft.
How big the vents are
The target both Harvia1 and HUUM2 give is the same: the air in the room should change six times in an hour. Harvia's KIP manual also sets a floor for the opening size, 10 sq in for the 3 and 4.5 kW heaters and 20 sq in for the 6 and 8 kW ones, and says the exhaust pipe must be twice the diameter of the supply pipe. HUUM gives 2 to 4 in for the supply pipe and 4 to 8 in for the exhaust, again at twice the supply.
The table runs those rules for every plan in the planner. The air column is the manual's target, six changes an hour in that room, not a measured airflow.
| Plan | Heater | Supply | Exhaust | Air at 6 changes an hour |
|---|---|---|---|---|
| 4 x 5 ft indoor | 4.5 kW | 4 in, 12.6 sq in | 8 in, 50.3 sq in | 14 cu ft a minute |
| 5 x 5 ft indoor | 4.5 kW | 4 in, 12.6 sq in | 8 in, 50.3 sq in | 18 cu ft a minute |
| 5 x 6 ft indoor | 6 kW | 6 in, 28.3 sq in | 12 in, 113.1 sq in | 21 cu ft a minute |
| 5 x 7 ft indoor | 6 kW | 6 in, 28.3 sq in | 12 in, 113.1 sq in | 25 cu ft a minute |
| 6 x 7 ft indoor | 8 kW | 6 in, 28.3 sq in | 12 in, 113.1 sq in | 29 cu ft a minute |
| 5 x 7 ft outdoor | 6 kW | 6 in, 28.3 sq in | 12 in, 113.1 sq in | 25 cu ft a minute |
| 6 x 7 ft outdoor | 8 kW | 6 in, 28.3 sq in | 12 in, 113.1 sq in | 29 cu ft a minute |
| 7 x 8 ft outdoor | 9 kW | 6 in, 28.3 sq in | 12 in, 113.1 sq in | 40 cu ft a minute |
| 8 x 8 ft wood-fired | Wood stove | 4 in, 12.6 sq in | 8 in, 50.3 sq in | 45 cu ft a minute |
| 7 x 10 ft outdoor | 10 kW | 8 in, 50.3 sq in | 12 in, 113.1 sq in | 49 cu ft a minute |
Round duct sizes, so the area is the duct's. The cover over each opening has to pass at least that area; check the free area its maker lists, because a louvered face often passes only about half its size. For wood stoves the sizes are planning sizes and the stove manual governs.
Where each vent goes
There are three openings and each has one job.
Supply: fresh air in, low by the heater.
Harvia says the supply vent goes below or next to the heater when the air moves on its own, and keeps it away from the temperature sensor. HUUM puts it at the middle of the heater or lower, about 16 in off the floor, and wants an adjustable valve on it. The planner puts it low on the heater wall beside the guard.Exhaust: used air out, low on the opposite wall.
Harvia calls the exhaust mandatory, near the floor and as far from the heater as you can get. HUUM puts it on the opposite wall about 24 in off the floor and at least 8 in higher than the supply. The planner follows Harvia for an electric heater and puts the exhaust low under the benches.Drying vent: high, closed while you bathe.
A 4 in opening near the ceiling on the wall opposite the heater. Keep it closed while the sauna heats and while you bathe, and open it after to dry the room. Harvia lists the drying vent as optional, and HUUM says that without one you can leave the door open after the bath.
The pattern is low, low, high: fresh air arrives by the heater, used air leaves from the opposite side, so the air crosses the whole room on the way, and the drying vent sits up high. The planner draws all three on the plan, and the designer shows them on the walls.
Indoor or outdoor
The three openings are the same in both. What changes is where the air goes.
Indoors, the exhaust goes to the house side or outdoors, and never into a closed attic. If it opens into a washroom, Harvia1 asks for a gap of at least 4 in under the sauna door, and HUUM2 asks for at least 4 in too, so the air has a way back in. Indoor rooms also need the insulation and foil vapor barrier taped to each sleeve all round, so the opening does not break the barrier.
Outdoors, run the exhaust to a hooded outlet with a screen so rain, snow and insects stay out. Each opening is a sleeve through the wall with the foil taped to it all round. The build guide shows where the sleeves go in the order of the build.
Wood-fired saunas
A wood stove burns the room's air, so the supply vent matters more. In the planner the supply sits low on the stove wall beside the stove, outside the stove's clearance zone, so the fire and the room share fresh air. Never close it while a fire burns, and put a CO alarm outside the hot room. The stove manual sets the real sizes and clearances. The wood-burning sauna stove guide covers the stove, the chimney and the floor protection.
Fans and mechanical ventilation
Both makers allow mechanical ventilation, and the rules change. Harvia1 puts the supply vent above the heater, in the wall or the ceiling, instead of below it. HUUM2 puts it at the middle of the heater or higher and keeps the exhaust on the opposite side at about 24 in off the floor. The drying vent stays under the ceiling opposite the heater.
That is as far as the manuals go, and so does this guide. We do not give a fan size, because neither manual does. If you want a fan, compare the cubic-feet-a-minute figure in the table with the fan maker's own rating, and ask your electrician to plan the circuit with you.
Common ventilation mistakes
Closing the supply with the heater on.
The heater needs the air, and so do you. Close the drying vent while you bathe; never close the supply.Leaving the drying vent open during the bath.
Both makers say to keep it shut while the sauna heats and while you bathe. Open it after, to dry the room.Putting the exhaust high, near the ceiling.
The manuals put the exhaust low on the far wall, near the floor for Harvia and about 24 in up for HUUM, never up by the ceiling.Putting the supply next to the temperature sensor.
Harvia's manual says to make sure the supply vent is not too near the temperature sensor. The planner keeps them apart.Skipping the gap under the door.
When the exhaust goes to a washroom, leave at least 4 in under the door.Using a smaller opening than the table says.
Check the free area of the vent cover, not its outside size.
Safety
Never seal a vent to keep heat in
Do not close or block the supply or exhaust with the heater on or a fire burning. A sauna that feels too hot or too stuffy needs its air path checked, not closed.
Depends on where you build
What the planner does not calculate
The vents follow the heater maker's rules: sizes, positions and the six-changes target. Natural draft depends on the temperature difference, the wind and your site, and is not calculated. On the first heat, light a smoke stick at the supply: if the smoke does not move toward the exhaust, the manual's other option is mechanical ventilation. Your local building department can add its own rules.
The rule of 200
You will see "the 200 rule" next to ventilation advice. It is not about vents. It says that the sauna's temperature in degrees Fahrenheit plus the relative humidity in percent should stay near 200, so the hotter the room, the drier it should be. Haven of Heat3, a sauna retailer, calls it a guideline and a general target, not a number you hold at every moment. It is a way to think about how hot and wet a session feels, and ventilation is one of the things that changes the humidity.
Next: size the heater for the room, then see the same room as a drawn sauna plan with the vents in place.
Sources
Every number in this guide that does not come from our own sauna designer was checked against these 3 documents, numbered in the order the text first cites them and read between Oct 9, 2026 and Nov 16, 2026. 3 are heater makers, codes and stores.