Plans we'd sweat in ourselves.

A sauna is a small building with a few hard rules. We wrote those rules into an engine, sourced every one, and priced the build from real store listings.

Last updated October 9, 2026

  • Rules from heater makersBench heights, room volume, vents and insulation come from Harvia and HUUM manuals and product data.
  • Prices with a dateEvery priced line names the store and the day it was read.
  • Run by Westernmost LLCA small product studio in Sheridan, Wyoming.

How the planner works

  1. Benches. The top bench sits 46 in under the ceiling, inside HUUM's 1100 to 1300 mm band. A lower tier steps 18 in down (our default). Seats are counted at 24 in each, Harvia's 60 cm.
  2. Heater. Room volume, plus 1.2 m3 for each m2 of glass (Harvia's rule), has to sit inside the maker's rated range. We pick the smallest model that covers it and list others that also fit.
  3. Air. An adjustable intake low by the heater, an exhaust with twice the area low on the opposite wall, and a drying vent high on that wall, as HUUM's manual lays out for gravity ventilation.
  4. Envelope. Mineral wool, a continuous foil vapor barrier with taped seams, a 3/4 in furring gap, then the boards, 4 in off the floor.
  5. Framing and shell. Studs at 16 in, ceiling joists at 16 in; outdoors, 2x6 walls on a skid floor over deck blocks with a 4/12 metal roof.
  6. Prices. Lumber, sheet goods and fasteners come from Home Depot and Lowe's listings read on October 8, 2026 (and September 30 for a few lines); sauna parts from Haven of Heat, The Sauna Heater, Twin Creeks Log Home Supply and Superarbor, read October 9, 2026. On October 9, Home Depot and Lowe's refused automated reads, so we did not refresh those lines that day.

What it does not do

It does not approve wiring, stove clearances or structures. Where a heater or stove manual differs from the planner, the manual wins. An electric heater is connected by a licensed electrician, and most towns want a permit for a new 240 V circuit and for an outdoor building.

Who we are

The Sauna Planner is a Westernmost LLC site, 30 N Gould St Ste R, Sheridan, WY 82801, USA. Write to hello@thesaunaplanner.com.

Sources

Every rule the planner applies comes from the heater maker's own manual or product data where one exists. Where a number is our own default, the designer says so next to it.

  1. 01International Residential Code 2021Sections R311.3 (landings at exterior doors), R311.7.5 (risers and treads) and R311.7.8 (handrails); R802.4.2 and R802.4.6 (ridge straps)R311.3: a landing or floor on each side of each exterior door, not less than the door's width and 36 in in the direction of travel. R311.3.2: doors other than the required egress door get landings or floors not more than 7-3/4 in below the top of the threshold; no top landing is needed where a stairway of not more than two risers is on the exterior side and the door does not swing over it. R311.7.5.1: risers not more than 7-3/4 in, the greatest within 3/8 in of the smallest. R311.7.5.2: treads not less than 10 in. R311.7.8: handrails on stairs with four or more risers. R802.4.2: rafters connected with a collar tie or ridge strap per R802.4.6. R802.4.6: ridge straps not less than 1-1/4 in x 20 gage, nailed to the top edge of each rafter with not fewer than three 10d common nails, the closest not nearer than 2-3/8 in to the rafter end.Read 2026-11-16 (2021 model text as adopted without amendment by Colorado; check the edition your town adopted)
  2. 02Southern Forest Products Association; Boise Cascade (after ASCE 7-16 Table C3.1-1a)Southern Pine Use Guide, design value Tables 1 and 2 and adjustment factors; Technical Note GE-1, weights of building materialsSouthern Pine No.2, 2 to 4 in thick and 5 to 6 in wide: Fb 1,000 psi, Fv 175 psi, E 1,400,000 psi. Wet service: Fb unchanged where Fb is 1,150 psi or less, E times 0.9. Load duration: 1.15 for snow. Boise Cascade GE-1: a wall of 2x6 studs at 16 in with gypsum, insulation and siding weighs 12 psf.Read 2026-10-21
  3. 03HUUMDROP 2.0 electric heater user manual (EU, v6)Room 2000 to 2300 mm high, never under 1900 mm; top bench 1100 to 1300 mm below the ceiling; 50 to 100 mm insulation, foil with taped joints, 10 mm gap behind the boards, 12 to 16 mm boards, 100 mm from the floor; supply air 50 to 100 mm at or below heater mid-height (400 mm), exhaust twice that on the opposite wall at least 200 mm higher (600 mm), drying vent under the ceiling; six air changes an hour; only a certified electrician connects the heater.Read 2026-10-09
  4. 04HarviaHow do I select the correct heater power?Each square meter of stone, glass or similar uninsulated surface adds as much load as 1.2 cubic meters of room volume.Read 2026-10-09 (search listing; the page answered 403)
  5. 05HarviaKIP heaters (KIP-30/45/60/80, B1 240 V): Instructions for installation and use, manual Y05-1516 B (08/26), the one edition this plan followsp. 14: distance from adjacent surfaces 3 in (KIP-30 and 45), 4 in (KIP-60), 5 in (KIP-80); floor area 16 to 30, 28 to 40 and 40 to 65 sq ft; room height at least 75 in in the USA; 240 V: 18.8 A 10/2, 25 A 10/2, 33.3 A 8/2. p. 16: "Use only dark joint grouts and floor coverings made of rock materials below and near the heater." p. 17: the air changes six times an hour; with pressure ventilation the supply is below or next to the heater; the exhaust is mandatory, near the floor as far from the heater as possible, its pipe two times the supply pipe's diameter; no supply size is given. p. 18: guard rail 2 in from the heater, at least 42 in from the heater top to the ceiling, heater bottom 7 to 12 in off the floor. p. 20: hanging screws 15-1/4 in apart, 20 in off the floor, heater 7 in off the floor. p. 21: a standard 2-pole breaker, no GFCI, 90 C copper wire on the sauna walls and ceiling; no breaker rating is given. p. 23: temperature sensor about 14 in from the ceiling and 14 in from the heater.Read 2026-11-16
  6. 06HarviaCilindro Half 240 V (HPCS9U1HB): US installation manual figures14 x 13 x 40 in floor-standing heater; 1.2 in to the wall and benches at the sides, 4 in in front, 35 in from the top to the ceiling, 2.8 in off the floor; 9 kW for 141 to 494 cu ft and 23 to 79 sq ft; minimum height 75 in.Read 2026-10-10
  7. 07Harvia; Finlandia (Harvia's US brand)Club K10G, K12.5G, K15G 240 V heaters: US owner's and installation manual (KG_USA Y05-0890) and US product pages10, 12.5 and 15 kW: 390 to 600, 500 to 750 and 630 to 1,000 cu ft; 60 to 94, 78 to 114 and 97 to 146 sq ft; minimum height 6.5 ft; 5, 6 and 6 in from adjacent surfaces and benches, 2-1/2 in to the wooden fence; 52 in from the heater top to the ceiling in the manual's figure (4.58 ft on the product page); 27.5 x 19.9 x 16.9 in, floor-standing, screwed to the floor; 12.6 kW 52.7 A with 6 AWG to a 2-pole, 2-breaker load center then (4) 10 AWG, 14.8 kW 61.7 A with 4 AWG then (4) 8 AWG, 90 C copper in the room; separate control unit (Xenio); inlet and outlet at least 30 sq in (10 kW) or 45 sq in (12.5 and 15 kW), five air changes an hour; ETL. The manual's text gives a 7 ft maximum ceiling, its figure 8 ft. Finlandia's table for the 10 kW: 41.7 A, 6 AWG, then (4) 10 AWG.Read 2026-10-20
  8. 08Scandia ManufacturingUltra Sauna heaters, small (3 to 4.5 kW), medium (6 to 9 kW) and large (12 to 18 kW), installation guides and brochure15 kW at 240 V single phase: 62.5 A, up to 1,428 cu ft (sizes based on a 7 ft ceiling, no minimum given); 26 x 18 x 29 in, wall-mounted 10-3/4 in off the floor; 8 in from the heater side to the wall, guard at least 26 in from the wall, 39 in from the heater top to a 7 ft ceiling, ceiling never over 8 ft; E control with its contactors ships with the heater and mounts outside the room; 4 x 10 in intake low behind the heater; 90 C wire in the room; UL listed. Each size has its own 208 V single-phase model at the same kW: small 30208 (14.4 A, up to 140 cu ft) and 45208 (21.7 A, up to 210), 16 x 10-3/4 x 23-1/4 in, 5 in side to wall, guard 16 in from the wall, 12 in off the floor, 45 in to a 7 ft ceiling; medium 60208 (28.9 A, 224 to 294 cu ft), 75208 (36.1 A, 280 to 448) and 90208 (43.3 A, 420 to 616), 16 x 14 x 28-3/4 in, 5 in side to wall, guard 19 in from the wall, 12 in off the floor, 38 in to a 7 ft ceiling; large 12208 (57.7 A, up to 980) and 15208 (72.2 A, up to 1,428). Medium install guide REV 3.31.17 (read 2026-11-16): guard at least 27 in W x 19 in D x 36-1/4 in H, top rail of the guard below the heater vent, three rails on each guarded face spaced 3-3/4 in apart, the guard rail at least 6 in from the out-vents, do not cut the guard down; A and B control tables at 240/208 V: 60 = 40 A, 75 = 40 A, 90 = 50 A breaker, supply 3 qty #8 including the ground, control to heater 3 qty #8 and 2 qty #14; vents adjustable with louvers, typical 4 x 10 in, intake immediately behind the heater as low as possible, exhaust as far from the intake as possible; no air change rate, no vent area and no GFCI rule.Read 2026-10-20
  9. 09HarviaLinear 18 Compact wood-burning heater, US product page and data sheet (WKLI18CPTM)14.3 kW; room 177 to 636 cu ft (5 to 18 m3); 30.31 x 17.72 x 20.08 in; to combustible material 11.81 in in front, 3.62 in at the sides and behind; 4.27 ft to the ceiling; chimney connection 115 mm, top or back; certificates CE, BImSchV 2 and EAC. No minimum room height on the page or the data sheet.Read 2026-10-21
  10. 10HarviaPro 26 wood-burning heater, US product page and data sheet (WKPR26M)26.6 kW; room 353 to 918 cu ft; minimum room height 6.56 ft; 31.89 x 16.93 x 20.08 in; 14.76 in to combustible material front, rear and sides; 4.2 ft to the ceiling. Certificates listed: CE and EAC; no US (UL) listing. The older code WK260 is shown as discontinued.Read 2026-10-20
  11. 11HarviaPro 36 wood-burning heater, US product page and data sheet (WKPR36M)Room 494 to 1,271 cu ft; minimum room height 6.56 ft on the page, 2060 mm (81.1 in) on the data sheet; 31.89 x 20.08 x 20.08 in; 19.69 in to combustible material front, rear and sides; 4.1 ft to the ceiling; chimney 115 mm, top or back. No kW on Harvia's pages (Haven of Heat lists 31 kW). Certificates listed: CE and EAC; no US (UL) listing.Read 2026-10-20
  12. 12HarviaM3 wood-burning heater, US product page (WKM3)Room 212 to 459 cu ft; to combustible material 11.81 in front and rear, 9.84 in each side; minimum room height 6.56 ft. Certificates listed on the page: CE and EAC only; we found no US (UL or ETL) listing for it.Read 2026-10-10
  13. 13HarviaPro 20 wood-burning heater, US product page (WKP200)300 mm (11.81 in) to combustible material front, rear and sides; 1.3 m to the ceiling; minimum room height 2 m. The page lists no US (UL or ETL) certificate.Read 2026-10-10
  14. 14Lamppa ManufacturingClassic Kuuma Legacy wood sauna stove: product page and owner's manual (August 2026 update)Listed by PFS-TECO to UL 1482 (solid-fuel type room heaters). Small, Medium, Large for 336 to 512, 512 to 780 and 780 to 1000 cu ft, $2,395, $2,595 and $2,795. Manual section 6, listed clearances: 48 in of clear space in front of the fuel-loading door, no shielding option; rear 8 in and side 7 in with the stove's shields and a non-combustible wall shield on a 1 in air gap (13-1/2 and 15-1/2 in with the stove shields only, 28 and 38 in without); wall shield from 4 in above the floor, 52 in tall, 8 in past the stove each side; non-combustible floor 8 in past the back and sides and 18 in in front of the base; ceiling 8 ft or more needs no ceiling shield, 88 in to under 96 in needs a ceiling shield on a 2 in ventilated air space; 6 in flue, single-wall connector to a listed Class A chimney.Read 2026-11-24
  15. 15International Residential Code 2021Table R802.5.2(1), rafter and ceiling joist heel joint connections; Tables R802.4.1(3), (5), (7), rafter spans; Table R802.5.1(1), ceiling joist spans; Table R502.3.1(2), floor joist spans4:12 roof, rafters 16 in on center, 12 ft span: 3, 3, 5 and 6 16d common nails per heel joint at 20, 30, 50 and 70 psf ground snow (earlier editions asked 4 at 30 psf; the plan uses 4); 24 ft span: 5, 6, 9 and 12. Ceiling joists, uninhabitable attic without storage (Table R802.5.1(1)), 2x6 spruce-pine-fir #2 at 16 in: 16 ft 11 in. Floor joists, 40 psf live and 10 psf dead (Table R502.3.1(2)), 2x6 southern pine #2 at 16 in: 9 ft 4 in. Ceiling joists nailed to the rafters at the plate are the rafter ties. 2x6 spruce-pine-fir #2 rafters at 16 in span 7 ft 11 in horizontally at 70 psf ground snow and 20 psf dead load.Read 2026-10-10 (2021 text as adopted by Colorado; check the edition your town adopted)
  16. 16International Residential Code 2021Table R602.3(1), fastening scheduleNail counts and spacing for each framing joint: plates to studs, double top plates, headers, ceiling joists and rafters to plates, rim and floor joists, and wood structural panel sheathing (6 in at edges, 12 in in the field for walls and floors, 6 in throughout on roofs).Read 2026-10-10 (2021 text as adopted by Colorado)
  17. 17International Residential Code 2021Tables R602.3(3), R602.10.4 and R602.10.5, wall sheathing used as bracingTable R602.10.4, method WSP: exterior wood structural panel sheathing fastened per Table R602.3(3), 6 in at the edges and 12 in in the field. Table R602.3(3): 24/16 panels 7/16 in and up, 8d common nails (2.5 x 0.131 in), 1.75 in penetration, studs at 16 in, 6 in edges and 12 in field, up to 170, 140 and 135 mph ultimate design wind in exposure B, C and D; footnote 3: plywood siding rated 16 o.c. or 24 o.c. may stand in for 24/16 panels, Wall-16 on studs at 16 in or less. Table R602.3(1) items 31 and 32 (19/32 to 3/4 in panels) send exterior wall sheathing to Table R602.3(3). Table R602.10.5, method CS-WSP, least panel length beside an opening, 8 ft wall: 24 in up to a 64 in opening, 26 at 68, 27 at 72, 30 at 76, 32 at 80, 35 at 84, 38 at 88, 43 at 92, 48 at 96; 9 ft wall: 27 up to 72, 29 at 76, 30 at 80, 32 at 84, 35 at 88, 37 at 92, 41 at 96, 44 at 100, 49 at 104, 54 at 108; interpolation allowed. R602.10.4.2: continuous sheathing covers every sheathable surface, above and below openings.Read 2026-11-17 (2021 text as adopted by Connecticut)
  18. 18HarviaHow to design a saunaThe seat for one person is usually 60 cm wide.Read 2026-10-09
  19. 19Haven of HeatHeater listings with the maker's room rangesHarvia KIP 4.5 kW 100 to 210 cu ft, 6 kW 170 to 300, 8 kW 250 to 425; Cilindro 9 kW 141 to 494; Harvia M3 212 to 459; Pro 20 283 to 706. Larger rooms use the makers' own ranges: Harvia Club 10, 12.5 and 15 kW, Scandia Ultra Large 15 kW, Harvia Pro 26 and Pro 36 (see their sources).Read 2026-10-09
  20. 20Haven of HeatWhat Is the Rule of 200 in a Sauna? Complete GuideSauna temperature in degrees Fahrenheit plus relative humidity in percent at or below 200; the page calls it a guideline and a general target, not a number held at every moment.Read 2026-10-29
  21. 21Green Building Advisor Q&AAir gap needed for foil radiant vapor barrier?An expert member: without an air gap, a radiant barrier is just a film that does pretty much nothing. Forum answer, not a standard.Read 2026-10-29
  22. 22Green Building Advisor Q&ATwo (air/vapor) barriers?Sauna wall with foil inside: an expert member says Tyvek is an air barrier but vapor permeable, a weather resistant barrier that blocks rain while letting the materials behind it dry. Forum answer, not a standard.Read 2026-10-29
  23. 23NFPA 70, National Electrical CodeArticle 424.4(B), branch-circuit sizing for fixed electric space-heating equipment (2020 text)Branch-circuit conductors are sized at no less than 125 percent of the load. Your jurisdiction's adopted edition and the heater's nameplate govern.Read 2026-10-09 (secondary summary)
  24. 24Cerrowire, after NFPA 70 (2017 NEC)Ampacity chart, copper conductors at 60 C (NM-B) and 75 C (THWN)Copper at 60 C: 14 AWG 15 A, 12 AWG 20, 10 AWG 30, 8 AWG 40, 6 AWG 55, 4 AWG 70, 3 AWG 85, 2 AWG 95. At 75 C: 8 AWG 50, 6 AWG 65, 4 AWG 85, 3 AWG 100, 2 AWG 115, 1 AWG 130. No temperature correction or adjustment factors applied.Read 2026-10-20