The short answer
A sauna with an electric heater needs its own 240 V circuit, sized at 125 percent of the heater's load. The 8 kW heater on the 6 x 7 ft outdoor sauna draws 33.3 A, so its conductors are sized for 41.7 A and the breaker is 45 A, 2-pole.
An electric sauna heater needs a dedicated 240 V circuit, with the wire and the breaker sized at 125 percent of the heater's load. A licensed electrician connects it. This guide gives you the numbers to plan with: the load, the breaker and the wire for every electric heater in the planner, and what each size in the free plans needs.
These are planning sizes. The heater's manual and nameplate come first and your electrician confirms them against the code your town has adopted. We do not do an electrical design, and nothing here replaces one.
Circuit, breaker and wire by heater size
The math is short. Amps are the heater's watts divided by the volts: kilowatts times 1,000, divided by 240. A heater runs for a long stretch, so the National Electrical Code4 treats it as a continuous load, and the branch-circuit conductors are sized at no less than 125 percent of it (the 424.4(B) rule for fixed electric heating equipment, read in a secondary summary). The breaker is the next standard size up from that figure.
The wire columns come from Cerrowire's copper ampacity chart, which lists 60 °C ratings for NM-B and 75 °C ratings for THHN/THWN-2. NM-B is the sheathed cable most people call Romex, and THHN/THWN-2 is the single wire run in conduit. Where the load is too big for NM-B in our table, the row says conduit.
| Heater | kW | Load at 240 V | At 125 percent | Breaker | THHN/THWN-2 in conduit | NM-B cable |
|---|---|---|---|---|---|---|
| KIP 4.5 kW | 4.5 | 18.8 A | 23.4 A | 25 A, 2-pole | 10 AWG copper | 10 AWG copper |
| KIP 6 kW | 6.0 | 25.0 A | 31.3 A | 35 A, 2-pole | 8 AWG copper | 8 AWG copper |
| KIP 8 kW | 8.0 | 33.3 A | 41.7 A | 45 A, 2-pole | 8 AWG copper | 6 AWG copper |
| Cilindro Half 9 kW | 9.0 | 37.5 A | 46.9 A | 50 A, 2-pole | 8 AWG copper | 6 AWG copper |
| Club K10G 10 kW package | 10.0 | 41.7 A | 52.1 A | 60 A, 2-pole | 6 AWG copper | 4 AWG copper |
| Club K12.5G 12.6 kW package | 12.6 | 52.5 A | 65.6 A | 70 A, 2-pole | 4 AWG copper | 4 AWG copper |
| Club K15G 14.8 kW package | 14.8 | 61.7 A | 77.1 A | 80 A, 2-pole | 4 AWG copper | 3 AWG copper |
| Ultra Large 15 kW | 15.0 | 62.5 A | 78.1 A | 80 A, 2-pole | 4 AWG copper | 3 AWG copper |
Planning sizes for 240 V single-phase heaters, copper conductors, no temperature or conduit-fill corrections. Some larger packages come with a separate power unit and a wire table of their own, and where the heater maker's table differs from this one, the maker's wins. Cable length and voltage drop are your electrician's call.
To size the circuit for one heater and your own room, use the sauna heater size calculator. It picks the heater for the room's volume and gives the amps, breaker and wire for that heater.
What each sample plan needs
Each of the 10 sizes in the free plans gets the heater that fits its room, so each has its own circuit. This is the same math as the table above, run on the plans.
| Plan | Heater | Load | Conductors sized for | Breaker |
|---|---|---|---|---|
| 4 x 5 ft indoor | 4.5 kW | 18.8 A | 23.4 A | 25 A, 2-pole |
| 5 x 5 ft indoor | 4.5 kW | 18.8 A | 23.4 A | 25 A, 2-pole |
| 5 x 6 ft indoor | 6 kW | 25.0 A | 31.3 A | 35 A, 2-pole |
| 5 x 7 ft indoor | 6 kW | 25.0 A | 31.3 A | 35 A, 2-pole |
| 6 x 7 ft indoor | 8 kW | 33.3 A | 41.7 A | 45 A, 2-pole |
| 5 x 7 ft outdoor | 6 kW | 25.0 A | 31.3 A | 35 A, 2-pole |
| 6 x 7 ft outdoor | 8 kW | 33.3 A | 41.7 A | 45 A, 2-pole |
| 7 x 8 ft outdoor | 9 kW | 37.5 A | 46.9 A | 50 A, 2-pole |
| 8 x 8 ft wood-fired | Wood stove | No heater circuit | None | None |
| 7 x 10 ft outdoor | 10 kW | 41.7 A | 52.1 A | 60 A, 2-pole |
A wood-fired sauna has no heater circuit, but a light still needs power, so the electrician has a smaller job there, not none. Open any plan in the designer and the electrical line updates when you change the room size and the heater changes with it.
Inside the hot room
The wiring that sits on the sauna walls and ceiling is held to a stricter standard than the run in your basement, because the room reaches sauna temperatures. What the heater makers say:
Heat-rated wire in the room.
Harvia's KIP manual says copper wire rated 90 °C (194 °F) must be used for all wiring on the sauna walls and the ceiling. HUUM's manual forbids a non-heat-resistant PVC-insulated cable as the heater's power cable. Your electrician picks the type that meets both the manual and the code.A standard 2-pole breaker.
The KIP manual asks for a standard 2-pole breaker and says not to use a GFCI breaker. HUUM's manual recommends connecting its heater without an earth-leakage circuit breaker. If your town's rules ask for GFCI protection on a circuit like this, that is a conversation between your electrician and the heater maker.Junction boxes low and waterproof.
HUUM says a junction box inside the sauna room should be waterproof and at most about 20 in (50 cm) from the floor. Heat collects under the ceiling, so low on the wall is also the coolest place for a connection.Controls and the temperature sensor.
Some heaters, like the KIP, have the controls built in; others, like the Club packages, use a separate control unit. Wherever the sensor sits, Harvia's manual says the fresh-air vent must not be too near it, and the planner keeps the two apart.A light made for a sauna.
Harvia's manual puts the light at least 6 in from the ceiling, not directly over the heater and not over the upper benches, and says it can go under the benches. Buy a fixture made for sauna temperatures.
The ventilation guide shows where the vents go, which matters for where the sensor and the light can sit.
Power to an outdoor cabin
An outdoor sauna needs the same heater circuit as an indoor one, plus a way to reach it. In practice that is a feeder from the house panel to the cabin, usually buried, ending at a panel or disconnect at the cabin, and then the heater circuit and the light from there. The outdoor sauna power section covers where this fits into the budget: a long trench can cost more than the cedar.
We do not give burial depths or the grounding rules for a detached building here. They depend on the wiring method, the code edition your town adopted and local amendments, and the NEC4 text is behind a paywall that we have not read. Ask your electrician for the depth and the cover they will use, and ask your building department what they inspect. The heater load in the table above is what your electrician needs to size the feeder.
Run that feeder before you fix the cabin's spot. Every foot between the panel and the cabin adds to the trench, the cable and the electrician's quote. The sauna cost calculator shows a published range for the electrician apart from the materials, for the circuit and the light, not for the trench.
Can you plug a sauna into a regular outlet?
Not any of the heaters in this planner. Every electric heater in the table above is 240 V and draws from 4.5 kW to 15.0 kW. The same heater on 120 V would draw twice the amps it draws on 240 V, so these are wired to a dedicated 240 V circuit and not to a wall plug.
Smaller heaters sold for 120 V plug-in use exist. We do not draw or size them, and we cannot verify their requirements. If you buy one, use the plug, the circuit and the room size its maker states, not our table.
How much electricity a sauna uses
A heater uses its kilowatt rating for every hour it runs at full power. So the 8 kW heater on the 6 x 7 ft outdoor sauna draws 8 kWh for an hour of full-power heating, and the heaters in our table range from 4.5 kWh to 15.0 kWh an hour. The thermostat cycles the heater off once the room is up to temperature, so a session uses less than the full-power figure times its length. We have no measured session figure and do not give one.
Who does the wiring
Safety
The heater circuit is not a DIY job
A 8 kW heater draws 33.3 A at 240 V for hours. The circuit conductors are sized at 125 percent of that, the breaker and wire come from the heater's manual, and the cable inside the hot room must be heat-rated. A licensed electrician does this, under a permit where your town requires one.
Depends on where you build
What the planner does not calculate
The planner gives the load, the breaker and the conductor size the heater manual and the NEC ask for. It does not design the feeder to a cabin, the panel capacity, the voltage drop or the grounding. Check with your local building department about permits and inspections.
Next: size the heater for your room, see the cabin side in the outdoor sauna guide, then follow the build guide for where the circuit sits in the order of the work.
Sources
Every number in this guide that does not come from our own sauna designer was checked against these 5 documents, numbered in the order the text first cites them and read between Oct 9, 2026 and Nov 16, 2026. 5 are heater makers, codes and stores.
- 1HarviaKIP heaters (KIP-30/45/60/80, B1 240 V): Instructions for installation and use, manual Y05-1516 B (08/26), the one edition this plan follows
- 2Harvia; Finlandia (Harvia's US brand)Club K10G, K12.5G, K15G 240 V heaters: US owner's and installation manual (KG_USA Y05-0890) and US product pages
- 3HUUMDROP 2.0 electric heater user manual (EU, v6)
- 4NFPA 70, National Electrical CodeArticle 424.4(B), branch-circuit sizing for fixed electric space-heating equipment (2020 text)
- 5Cerrowire, after NFPA 70 (2017 NEC)Ampacity chart, copper conductors at 60 C (NM-B) and 75 C (THWN)




